U.S. Nuclear Regulatory Commission Operations Center Event Reports For 08/30/96 - 09/03/96 ** EVENT NUMBERS ** 30941 30942 30943 30944 30945 30946 30947 30948 30949 +----------------------------------+ +-----------------------+ |POWER REACTOR | |EVENT NUMBER: 30941 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |FACILITY: MILLSTONE REGION: 1 |NOTIFICATION DATE: 08/30/96 | |UNIT: [ ] [ ] [3] STATE: CT |NOTIFICATION TIME: 13:32 [ET]| |RX TYPE: [1] GE-3,[2] CE,[3] W-4-LP |EVENT DATE: 08/30/96 | +------------------------------------------------+EVENT TIME: 13:13[EDT]| |NRC NOTIFIED BY: TOM LYONS |LAST UPDATE DATE: 08/30/96 | |HQ OPS OFFICER: RUDY KARSCH +-----------------------------+ +------------------------------------------------+ NOTIFICATIONS | |EMERGENCY CLASS: NOT APPLICABLE +-----------------------------+ |10 CFR SECTION: |ROBERT BORES RDO | |AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | | | | | | | | | | | | | | +-----+----------+-------+--------+--------------+--+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ | | | | | | | | | 3 | N N 0 COLD SHUTDOWN | 0 COLD SHUTDOWN | +-----+---------------------------------------------+--------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | DURING THE POST-ACCIDENT RECIRCULATION COOLING PHASE OF AN EVENT, THE HIGH | | HEAD SAFETY INJECTION PUMPS AND THE CHARGING PUMPS COULD EXPERIENCE A | | RUNOUT CONDITION. | | | | DURING THE POST-ACCIDENT RECIRCULATION COOLING PHASE OF AN EVENT, THE | | RECIRCULATION SPRAY PUMPS TAKE SUCTION FROM THE CONTAINMENT SUMP, AND THE | | DISCHARGE FROM THESE PUMPS PROVIDES SUCTION TO BOTH THE HIGH HEAD SAFETY | | INJECTION PUMPS (TWO) AND THE CHARGING PUMPS (THREE). THROTTLE VALVES IN | | THE INJECTION PATH ARE USED TO BALANCE THE FLOWS. | | | | INITIAL TESTING AND SET UP WAS PERFORMED USING A TANK AS THE SUCTION SOURCE | | FOR THE PUMPS. THE LICENSEE HAS DISCOVERED THAT WHEN THE RECIRCULATION | | SPRAY PUMPS ARE THE SUCTION SOURCE, AS THEY WOULD BE AFTER AN ACCIDENT, THE | | HIGHER SUCTION PRESSURE PROVIDED BY THE PUMPS MIGHT CAUSE RUNOUT OF THE | | FIVE DOWN STREAM PUMPS. ADJUSTING THE INJECTION PATH THROTTLE VALVES HAS | | NOT SOLVED THE PROBLEM. THE LICENSEE WILL INSTALL ORIFICE PLATES IN THE | | FOUR INJECTION LINES TO LIMIT FLOW AND PREVENT PUMP RUNOUT. THE ADEQUACY | | OF THIS INSTALLATION WILL BE CONFIRMED BY FLOW TESTING. | | | | THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR. | +------------------------------------------------------------------------------+ +----------------------------------+ +-----------------------+ |POWER REACTOR | |EVENT NUMBER: 30942 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |FACILITY: HADDAM NECK REGION: 1 |NOTIFICATION DATE: 08/30/96 | |UNIT: [1] [ ] [ ] STATE: CT |NOTIFICATION TIME: 16:06 [ET]| |RX TYPE: [1] W-4-LP |EVENT DATE: 08/30/96 | +------------------------------------------------+EVENT TIME: 15:35[EDT]| |NRC NOTIFIED BY: DAVID REILLY |LAST UPDATE DATE: 08/30/96 | |HQ OPS OFFICER: RUDY KARSCH +-----------------------------+ +------------------------------------------------+ NOTIFICATIONS | |EMERGENCY CLASS: NOT APPLICABLE +-----------------------------+ |10 CFR SECTION: |ROBERT BORES RDO | |AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | | | | | | | | | | | | | | +-----+----------+-------+--------+--------------+--+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ | 1 | N N 0 COLD SHUTDOWN | 0 COLD SHUTDOWN | | | | | | | | | +-----+---------------------------------------------+--------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | THE LICENSEE MAY NOT BE ABLE TO FULFILL THE REQUIREMENTS OF ITS FSAR | | ACCIDENT ANALYSIS TO ISOLATE FEEDWATER FLOW TO A FAULTED STEAM GENERATOR | | WITHIN TEN MINUTES BY OPERATOR ACTION FROM THE CONTROL ROOM. THE AIR | | OPERATORS ON THE FEEDWATER ISOLATION VALVES ARE TOO UNDER POWERED TO CLOSE | | THE VALVES AGAINST THE DIFFERENTIAL PRESSURES THAT OCCUR IF THERE IS A | | BREAK WITH BOTH THE MAIN AND AUXILIARY FEED PUMPS RUNNING. THE LICENSEE IS | | INVESTIGATING SEVERAL OPTIONS TO CORRECT THIS PROBLEM. THE PROBLEM WILL BE | | CORRECTED PRIOR TO RESTART OF THE UNIT. | | | | THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR. | +------------------------------------------------------------------------------+ +----------------------------------+ +-----------------------+ |GENERAL INFORMATION or OTHER | |EVENT NUMBER: 30943 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |LICENSEE: COGEMA MINING CO |NOTIFICATION DATE: 08/30/96 | | CITY: 90 MI NNE OF CA REGION: 4 |NOTIFICATION TIME: 16:20 [ET]| | COUNTY: JOHNSON STATE: WY |EVENT DATE: 08/29/96 | |LICENSE#: SUA 1341 AGREEMENT: N |EVENT TIME: 14:00[MDT]| | DOCKET: |LAST UPDATE DATE: 08/30/96 | | +-----------------------------+ | |PERSON ORGANIZATION| | |DALE POWERS RDO | | | | +------------------------------------------------+ | |NRC NOTIFIED BY: JOHN VASELIN | | |HQ OPS OFFICER: RUDY KARSCH | | +------------------------------------------------+ | |EMERGENCY CLASS: NOT APPLICABLE | | |10 CFR SECTION: | | |NINF INFORMATION ONLY | | | | | | | | | | | | | | +------------------------------------------------+-----------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | MONITORING WELL NUMBER SSM3 FOR IRIGARAY MINE UNIT 2 WAS CONFIRMED TO BE IN | | EXCURSION STATUS FOR CHLORIDES AND CONDUCTIVITY. THE CHLORIDE LIMIT IS | | 38.5 PPM, AND READINGS WERE 44.4 AND 42.9 PPM. THE CONDUCTIVITY LIMIT IS | | 1,451 æMHO/CM, AND READINGS WERE 1,636 AND 1,572 æMHO/CM. THERE WAS NO | | URANIUM DETECTED IN THE TEST SAMPLES. THIS MINE HAS BEEN SHUT DOWN, AND | | THE LICENSEE BELIEVES THE EXCURSIONS ARE CAUSED BY THE RECLAMATION PROCESS. | | THE LICENSEE ALSO BELIEVES THAT THIS CONDITION DOES NOT REPRESENT A PUBLIC | | HEALTH HAZARD. | | | | (REFER TO EVENT NUMBERS 30369 AND 30882 FOR SIMILAR EVENTS.) | +------------------------------------------------------------------------------+ +----------------------------------+ +-----------------------+ |POWER REACTOR | |EVENT NUMBER: 30944 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |FACILITY: BEAVER VALLEY REGION: 1 |NOTIFICATION DATE: 08/30/96 | |UNIT: [ ] [2] [ ] STATE: PA |NOTIFICATION TIME: 23:49 [ET]| |RX TYPE: [1] W-3-LP,[2] W-3-LP |EVENT DATE: 08/30/96 | +------------------------------------------------+EVENT TIME: 20:49[EDT]| |NRC NOTIFIED BY: TOM McCOOL |LAST UPDATE DATE: 08/30/96 | |HQ OPS OFFICER: RUDY KARSCH +-----------------------------+ +------------------------------------------------+ NOTIFICATIONS | |EMERGENCY CLASS: NOT APPLICABLE +-----------------------------+ |10 CFR SECTION: |ROBERT BORES RDO | |ARPS 50.72(b)(2)(ii) RPS ACTUATION | | | | | | | | | | | | | | +-----+----------+-------+--------+--------------+--+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ | | | | | 2 | M/R Y 0 STARTUP | 0 HOT STANDBY | | | | | +-----+---------------------------------------------+--------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | MANUAL TRIP DUE TO UNEXPECTED REACTOR COOLDOWN | | | | WHILE SHUTTING DOWN FOR A REFUELING OUTAGE WITH REACTOR POWER AT 10E-7 AMPS | | ON THE INTERMEDIATE RANGE, REACTOR COOLANT TEMPERATURE BEGAN DROPPING FROM | | THE NORMAL NO-LOAD VALUE OF 547øF. THE OPERATORS ISOLATED STEAM GENERATOR | | BLOWDOWN AND MAIN CONDENSER STEAM DUMPS (EVEN THOUGH THE DUMP VALVES WERE | | INDICATING CLOSED), BUT TEMPERATURE CONTINUED TO DROP. WHEN REACTOR COOLANT | | TEMPERATURE REACHED 541øF, A MANUAL REACTOR TRIP WAS ORDERED. ALL CONTROL | | RODS INSERTED FULLY FOLLOWING THE TRIP. THERE WERE NO ENGINEERED SAFETY | | FEATURE ACTUATIONS. | | | | THE LICENSEE OBSERVED THAT THE LEVEL IN THE "A" STEAM GENERATOR WAS | | SLIGHTLY HIGHER THAN IN THE "B" AND "C" STEAM GENERATORS. THE LICENSEE | | SUSPECTED THAT FEEDWATER WAS LEAKING INTO THE "A" STEAM GENERATOR CAUSING | | THE COOLDOWN. WHEN THE FEEDWATER BYPASS REGULATING VALVE'S BLOCK VALVE WAS | | CLOSED, THE "A" STEAM GENERATOR LEVEL STOPPED RISING, AND REACTOR COOLANT | | TEMPERATURE RETURNED TO 547øF. THE MAIN CONDENSER WAS RETURNED TO SERVICE | | AND IS BEING USED FOR TEMPERATURE CONTROL. | | | | THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR. | +------------------------------------------------------------------------------+ +----------------------------------+ +-----------------------+ |POWER REACTOR | |EVENT NUMBER: 30945 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |FACILITY: HADDAM NECK REGION: 1 |NOTIFICATION DATE: 08/31/96 | |UNIT: [1] [ ] [ ] STATE: CT |NOTIFICATION TIME: 13:52 [ET]| |RX TYPE: [1] W-4-LP |EVENT DATE: 08/31/96 | +------------------------------------------------+EVENT TIME: 13:27[EDT]| |NRC NOTIFIED BY: RICHARD WILLIS |LAST UPDATE DATE: 08/31/96 | |HQ OPS OFFICER: RUDY KARSCH +-----------------------------+ +------------------------------------------------+ NOTIFICATIONS | |EMERGENCY CLASS: NOT APPLICABLE +-----------------------------+ |10 CFR SECTION: |ROBERT BORES RDO | |ADAS 50.72(b)(2)(i) DEG/UNANALYZED COND | | | | | | | | | | | | | | +-----+----------+-------+--------+--------------+--+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ | 1 | N N 0 COLD SHUTDOWN | 0 COLD SHUTDOWN | | | | | | | | | +-----+---------------------------------------------+--------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | OPERATORS DISCOVERED A PIN HOLE LEAK IN THE "A" RESIDUAL HEAT REMOVAL (RHR) | | HEAT EXCHANGER INLET ISOLATION VALVE. | | | | DURING A WALKDOWN, AN OPERATOR NOTICED A BORIC ACID DEPOSIT ON THE BODY OF | | THE "A" RHR HEAT EXCHANGER INLET ISOLATION VALVE. THE DEPOSIT RESULTED | | FROM A PIN HOLE LEAK IN THE VALVE BODY. THE LEAK RATE IS LESS THAN 0.5 | | mL/MIN. THIS IS NOT PRESSURE BOUNDARY LEAKAGE. THE LICENSEE'S HEALTH | | PHYSICS DEPARTMENT CONDUCTED A SURVEY. RADIATION EXPOSURE FROM THE LEAKAGE | | IS SO LOW THAT ACCESS WAS NOT RESTRICTED. A TEMPORARY REPAIR WILL BE MADE | | UNTIL THE FUEL IS OFF-LOADED. AT THAT TIME, WHEN RHR IS NO LONGER NEEDED, | | THE LICENSEE WILL MAKE A PERMANENT REPAIR. OTHER VALVES IN THE RHR SYSTEM | | HAVE BEEN INSPECTED AND APPEAR TO BE OKAY. | | | | THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR AND THE STATE GOVERNMENT. | +------------------------------------------------------------------------------+ +----------------------------------+ +-----------------------+ |POWER REACTOR | |EVENT NUMBER: 30946 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |FACILITY: SAINT LUCIE REGION: 2 |NOTIFICATION DATE: 08/31/96 | |UNIT: [1] [ ] [ ] STATE: FL |NOTIFICATION TIME: 22:45 [ET]| |RX TYPE: [1] CE,[2] CE |EVENT DATE: 08/31/96 | +------------------------------------------------+EVENT TIME: 20:20[EDT]| |NRC NOTIFIED BY: JACK BREEN |LAST UPDATE DATE: 08/31/96 | |HQ OPS OFFICER: RUDY KARSCH +-----------------------------+ +------------------------------------------------+ NOTIFICATIONS | |EMERGENCY CLASS: NOT APPLICABLE +-----------------------------+ |10 CFR SECTION: |KENNETH BARR RDO | |ARPS 50.72(b)(2)(ii) RPS ACTUATION | | | | | | | | | | | | | | +-----+----------+-------+--------+--------------+--+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ | 1 | M/R Y 58 POWER OPERATION | 0 HOT STANDBY | | | | | | | | | +-----+---------------------------------------------+--------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | MANUAL REACTOR TRIP IN ANTICIPATION OF MAIN TRANSFORMER FAILURE | | | | AT 1903 EDT, A DECREASE IN UNIT 1 POWER WAS INITIATED DUE TO A INCREASE IN | | GAS VOLUME IN THE "1B" MAIN TRANSFORMER. AT 58% POWER, THE REACTOR WAS | | MANUALLY TRIPPED BECAUSE GAS VOLUME IN THE TRANSFORMER WAS STILL | | INCREASING. ALL CONTROL RODS FULLY INSERTED AFTER THE TRIP. THE UNIT IS | | STABLE IN MODE 3. DECAY HEAT REMOVAL IS VIA THE MAIN CONDENSER. THE MAIN | | TRANSFORMER HAS BEEN ISOLATED, AND TROUBLESHOOTING OF THE TRANSFORMER IS | | UNDER WAY. | | | | THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR. | +------------------------------------------------------------------------------+ +----------------------------------+ +-----------------------+ |POWER REACTOR | |EVENT NUMBER: 30947 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |FACILITY: INDIAN POINT REGION: 1 |NOTIFICATION DATE: 09/01/96 | |UNIT: [2] [ ] [ ] STATE: NY |NOTIFICATION TIME: 05:30 [ET]| |RX TYPE: [2] W-4-LP,[3] W-4-LP |EVENT DATE: 09/01/96 | +------------------------------------------------+EVENT TIME: 05:15[EDT]| |NRC NOTIFIED BY: LEEJOY |LAST UPDATE DATE: 09/01/96 | |HQ OPS OFFICER: BOB STRANSKY +-----------------------------+ +------------------------------------------------+ NOTIFICATIONS | |EMERGENCY CLASS: NOT APPLICABLE +-----------------------------+ |10 CFR SECTION: |BORES RDO | |ANHU 50.72(b)(1)(iii) HURRICANE | | | | | | | | | | | | | | +-----+----------+-------+--------+--------------+--+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ | 2 | N Y 100 POWER OPERATION | 100 POWER OPERATION | | | | | | | | | +-----+---------------------------------------------+--------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | HURRICANE WITHIN 500 NAUTICAL MILES OF PLANT. | | | | AT 0515, THE LICENSEE WAS NOTIFIED THAT THE NATIONAL WEATHER SERVICE HAS | | ISSUED A HURRICANE WARNING FOR THE AREA EXTENDING FROM WATCH HILL, RHODE | | ISLAND, TO THE MERRIMACK RIVER IN MASSACHUSETTS. THE PRESENT LOCATION OF | | HURRICANE EDOUARD IS WITHIN 500 NAUTICAL MILES OF THE SITE. THE LICENSEE | | HAS ENTERED ABNORMAL OPERATING PROCEDURE AOI-28.0.7 AND HAS BEGUN HOURLY | | TRACKING OF THE STORM. | | | | THE NRC RESIDENT INSPECTOR WILL BE INFORMED OF THIS NOTIFICATION. | +------------------------------------------------------------------------------+ +----------------------------------+ +-----------------------+ |POWER REACTOR | |EVENT NUMBER: 30948 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |FACILITY: MAINE YANKEE REGION: 1 |NOTIFICATION DATE: 09/01/96 | |UNIT: [1] [ ] [ ] STATE: ME |NOTIFICATION TIME: 13:30 [ET]| |RX TYPE: [1] CE |EVENT DATE: 08/31/96 | +------------------------------------------------+EVENT TIME: 19:55[EDT]| |NRC NOTIFIED BY: LARRY GRIMAARD |LAST UPDATE DATE: 09/01/96 | |HQ OPS OFFICER: RUDY KARSCH +-----------------------------+ +------------------------------------------------+ NOTIFICATIONS | |EMERGENCY CLASS: NOT APPLICABLE +-----------------------------+ |10 CFR SECTION: |ROBERT BORES RDO | |APRE 50.72(b)(2)(vi) OFFSITE NOTIFICATION | | | | | | | | | | | | | | +-----+----------+-------+--------+--------------+--+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ | 1 | N N 0 HOT STANDBY | 0 HOT STANDBY | | | | | | | | | +-----+---------------------------------------------+--------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | THE LICENSEE ISSUED A PRESS RELEASE BECAUSE A CONTRACT EMPLOYEE PERFORMING | | FIRE WATCH DUTIES WAS REMOVED FROM THE SITE VIA AN AMBULANCE. THE | | INDIVIDUAL APPARENTLY SUFFERED A HEART ATTACK AND SUBSEQUENTLY DIED. | | | | THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR. | +------------------------------------------------------------------------------+ +----------------------------------+ +-----------------------+ |OTHER NUCLEAR MATERIAL | |EVENT NUMBER: 30949 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |LICENSEE: BICRON |NOTIFICATION DATE: 09/02/96 | | CITY: NEWBURY REGION: 3 |NOTIFICATION TIME: 14:22 [ET]| | COUNTY: STATE: OH |EVENT DATE: 08/02/96 | |LICENSE#: 34-06558-05 AGREEMENT: N |EVENT TIME: 10:15[EDT]| | DOCKET: |LAST UPDATE DATE: 09/02/96 | | +-----------------------------+ | |PERSON ORGANIZATION| | |JOHN JACOBSON RDO | | | | +------------------------------------------------+ | |NRC NOTIFIED BY: JEFF KENNEDY | | |HQ OPS OFFICER: LEIGH TROCINE | | +------------------------------------------------+ | |EMERGENCY CLASS: NOT APPLICABLE | | |10 CFR SECTION: | | |BAB2 20.2201(a)(1)(ii) LOST/STOLEN LNM>10X | | | | | | | | | | | | | | +------------------------------------------------+-----------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | BICRON OF NEWBURY, OHIO, REPORTED A LOST 0.012-MICROCURIE AMERICIUM-241 | | SOURCE. | | | | BICRON UTILIZES AMERICIUM-241 SOURCES TO MANUFACTURE SODIUM IODIDE | | DETECTORS WITH A PULSAR UNIT INSIDE TO GIVE A STEADY COUNT RATE. DURING | | THE PERFORMANCE OF THIS PROCESS AT APPROXIMATELY 1015 ON AUGUST 2, 1996, A | | 0.012-MICROCURIE AMERICIUM-241 CAPSULE POPPED OUT OF THE HANDS OF AN | | OPERATOR AND DISAPPEARED. (THE REPORTING LIMIT IS 0.01 MICROCURIES.) IN | | AN EFFORT TO SEARCH FOR THE MISSING CAPSULE, THE LICENSEE COMPLETELY | | DISMANTLED THE SMALL ROOM THAT THE OPERATOR WAS WORKING IN, BUT THE | | 3/8-INCH DIAMETER BY 3/8-INCH LONG SOURCE (DETECTOR UNIT) WAS NOT FOUND. | | THE LICENSEE CURRENTLY BELIEVES THAT THE SOURCE MAY HAVE GOTTEN CAUGHT IN | | THE CUFF OF THE OPERATOR'S LAB COAT WHEN IT FELL FROM THE OPERATOR'S HANDS | | AND THAT IT MAY HAVE SUBSEQUENTLY BEEN LOST FROM THERE. THE LICENSEE DOES | | NOT BELIEVE THAT THERE IS AN EXTERIOR EXPOSURE RISK ASSOCIATED WITH THIS | | EVENT. | | | | THE LICENSEE NOTIFIED NRC REGION 3 (MICHAEL FONZER) LAST WEEK AND PLANS TO | | FOLLOWUP WITH A WRITTEN NOTICE. (REFER TO THE HOO LOG FOR A LICENSEE | | CONTACT ADDRESS AND TELEPHONE NUMBERS.) | +------------------------------------------------------------------------------+