U.S. Nuclear Regulatory Commission Operations Center Event Reports For 08/22/94 - 08/23/94 ** EVENT NUMBERS ** 27694 27695 +----------------------------------+ +-----------------------+ |POWER REACTOR | |EVENT NUMBER: 27694 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |FACILITY: LIMERICK REGION: 1 |NOTIFICATION DATE: 08/22/94 | |UNIT: [1] [ ] [ ] STATE: PA |NOTIFICATION TIME: 14:04 [ET]| |RX TYPE: [1] GE-4,[2] GE-4 |EVENT DATE: 08/22/94 | +------------------------------------------------+EVENT TIME: 12:20[EDT]| |NRC NOTIFIED BY: ROBERT DELANEY |LAST UPDATE DATE: 08/22/94 | |HQ OPS OFFICER: DOUG WEAVER +-----------------------------+ +------------------------------------------------+ NOTIFICATIONS | |EMERGENCY CLASS: NOT APPLICABLE +-----------------------------+ |10 CFR SECTION: |JOHN KINNEMAN RDO | |AESF 50.72(b)(2)(ii) ESF ACTUATION | | | | | | | | | | | | | | +-----+----------+-------+--------+--------------+--+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ | 1 | N Y 100 POWER OPERATION | 100 POWER OPERATION | | | | | | | | | +-----+---------------------------------------------+--------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | FAILURE OF CHANNEL D OF THE REACTOR ENCLOSURE VENTILATION EXHAUST RADIATION | | MONITORING SYSTEM CAUSED A GROUP 6C ESF ISOLATION. | | | | "AT 1220 EDT, THE UNIT 1, D CHANNEL OF THE REACTOR ENCLOSURE VENTILATION | | EXHAUST RADIATION MONITORING SYSTEM (RISH-026-1K609D) TRIPPED AND CAUSED A | | GROUP 6C ISOLATION. IT WAS VERIFIED THAT NO HIGH RADIATION CONDITION | | EXISTED AND NO INCREASE WAS IN PROGRESS. NO TESTING OR MANIPULATIONS WERE | | BEING PERFORMED. SYSTEMS AFFECTED BY THE ISOLATION WERE THE PRIMARY | | CONTAINMENT SAMPLE, POST LOCA RECOMBINERS, REACTOR RECIRCULATING PUMP SEAL | | PURGE, PRIMARY CONTAINMENT INSTRUMENT GAS BARRIER BLOCK AND VENTS AND | | NITROGEN MAKE-UP BARRIER BLOCK AND VENTS. DURING THE INVESTIGATION, THE | | RISH-026-1K609D WAS FOUND TO BE CAUSING AN INOP TRIP WHICH SUBSEQUENTLY | | RESET. THE RADIATION MONITOR INDICATES NORMAL, AND PLANT STAFF ARE | | INVESTIGATING THE POSSIBLE CAUSE." | | | | THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR. | +------------------------------------------------------------------------------+ +----------------------------------+ +-----------------------+ |POWER REACTOR | |EVENT NUMBER: 27695 | +----------------------------------+ +-----------------------+ +------------------------------------------------+-----------------------------+ |FACILITY: FERMI REGION: 3 |NOTIFICATION DATE: 08/22/94 | |UNIT: [2] [ ] [ ] STATE: MI |NOTIFICATION TIME: 18:46 [ET]| |RX TYPE: [2] GE-4 |EVENT DATE: 08/22/94 | +------------------------------------------------+EVENT TIME: 17:10[EDT]| |NRC NOTIFIED BY: BOB GAILLIEZ |LAST UPDATE DATE: 08/22/94 | |HQ OPS OFFICER: DOUG WEAVER +-----------------------------+ +------------------------------------------------+ NOTIFICATIONS | |EMERGENCY CLASS: NOT APPLICABLE +-----------------------------+ |10 CFR SECTION: |MIKE MCCANN RDO | |AINC 50.72(b)(2)(iii)(C) POT UNCNTRL RAD REL | | | | | | | | | | | | | | +-----+----------+-------+--------+--------------+--+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ | 2 | N N 0 REFUELING | 0 REFUELING | | | | | | | | | +-----+---------------------------------------------+--------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | ISOLATION VALVE WILL NOT FUNCTION UNDER ACCIDENT CONDITIONS. | | | | DURING ENGINEERING REVIEW OF THE DESIGN OF THE REACTOR RECIRCULATION PUMP | | SEAL PURGE LINE AIR OPERATED ISOLATION VALVES, IT WAS DISCOVERED THAT THE | | LINE WILL NOT BE PROPERLY ISOLATED UNDER ACCIDENT CONDITIONS. THESE VALVES | | HAVE INADEQUATE CLOSING FORCE TO SHUT THE VALVES DURING ACCIDENT | | CONDITIONS. | | | | THE ENGINEERING DEPARTMENT IS STILL INVESTIGATING POSSIBLE SOLUTIONS TO THE | | PROBLEM. | | | | THE LICENSEE WILL INFORM THE NRC RESIDENT INSPECTOR. | +------------------------------------------------------------------------------+