Headquarters Daily Report FEBRUARY 14, 1997 *************************************************************************** REPORT NEGATIVE NO INPUT ATTACHED INPUT RECEIVED RECEIVED HEADQUARTERS û REGION I û REGION II û REGION III û REGION IV û PRIORITY ATTENTION REQUIRED MORNING REPORT - REGION III FEB. 14, 1997 Licensee/Facility: Notification: Commonwealth Edison Co. MR Number: 3-97-0029 Byron 1 Date: 02/14/97 Byron,Illinois RI VIA TELECON AND PC Dockets: 50-454 PWR/W-4-LP Subject: FAILED FEED PUMP SHAFT GLAND SEAL LINE AND EARLY ENTRY INTO A PLANNED SHUTDOWN AND OUTAGE Discussion: AT APPROXIMATELY 11:00 P.M. (CST) ON FEBRUARY 13, 1997, A CRACK DEVELOPED IN A WELD ON A PUMP SHAFT GLAND SEAL WATER RETURN LINE FOR THE 1C TURBINE DRIVEN MAIN FEEDWATER PUMP. THE CRACK RESULTED IN A STEAM LEAK. THE LICENSEE WAS IN THE PROCESS OF RETURNING THE 1C FEEDWATER PUMP TO SERVICE FOLLOWING MAINTENANCE AT THE TIME OF THE EVENT. THE LICENSEE WAS UNABLE TO ISOLATE THE LEAKING WATER AND STEAM COMING FROM THE HEATER DRAIN TANK BACK THROUGH THE FAILED LINE. UNIT 1 POWER WAS REDUCED TO APPROXIMATELY 25 PERCENT TO ALLOW ISOLATION OF THE FEEDWATER HEATERS AND REMOVE THE HEAT INPUT TO THE HEATER DRAIN TANK. ON 2/14/97, AS OF 8:00 A.M. CST THE LICENSEE WAS PREPARING TO SHUTDOWN UNIT 1 AND BEGIN A SCHEDULED MAINTENANCE OUTAGE 24 HOURS EARLIER THAN ORIGINALLY PLANNED. THE STEAM LEAK DID NOT INVOLVE ANY SAFETY-RELATED EQUIPMENT. ALL AUXILIARY FEEDWATER PUMPS WERE OPERABLE. THE CAUSE OF THE CRACK IS UNDER INVESTIGATION BY THE LICENSEE. THE LICENSEE WAS SCHEDULED TO BEGIN A 12 DAY MAINTENANCE OUTAGE ON FEBRUARY 15, 1997. REACTOR CONTAINMENT FAN COOLERS (RCFC) 1D AND 1C WERE EXHIBITING ESSENTIAL SERVICE WATER FLOW REDUCTION FROM THE NOMINAL VALUES DURING MONTHLY SURVEILLANCES. THE LICENSEE IS PLANNING TO INSTALL A MODIFICATION TO BACKFLUSH THE HEAT EXCHANGERS AND IDENTIFY THE CAUSE OF THE FLOW REDUCTION. SILT BUILDUP IS SUSPECTED AND IS THE SUBJECT OF ENFORCEMENT DISCUSSED IN INSPECTION REPORT (50-454 & 455/96009.) Regional Action: THE RESIDENT INSPECTOR IS MONITORING THE ACTIVITIES. Contact: R. D. LANKSBURY (630)829-9631 _