Headquarters Daily report JUNE 22, 1995 *************************************************************************** REPORT NEGATIVE NO INPUT ATTACHED INPUT RECEIVED RECEIVED HEADQUARTERS X REGION I X REGION II X REGION III X REGION IV X *************************************************************************** PRIORITY ATTENTION REQUIRED MORNING REPORT - REGION IV JUNE 22, 1995 Licensee/Facility: Notification: Texas Utilities Electric Co. MR Number: 4-95-0087 Comanche Peak 2 Date: 06/22/95 Glen Rose,Texas Resident Inspector Via Telephone Dockets: 50-446 PWR/W-4-LP Subject: TURBINE DRIVEN AUXILIARY FEEDWATER PUMP OVERSPEED TRIP Reportable Event Number: N/A Discussion: While starting the Unit 2 turbine driven auxiliary feedwater (TDAFW) pump on June 21, 1995, the turbine tripped on overspeed. The system engineer was monitoring the turbine startup and reported that the governor did not move during the start. The pump turbine reportedly emitted a large amount of water out the stack vent on top of the safeguards building. Additionally, the sentinel valve at the top the turbine casing emitted water continuously during the start. The turbine tripped on overspeed approximately 13 seconds after the start and reached approximately 5000 rpm. During the turbine warmup being performed just prior to the start, the governor valve reportedly exhibited a jerky motion. The pump was being run to further investigate unusual noises detected four days earlier. On June 16, the TDAFW pump was started for a routine surveillance test. During the test, operators noted a change in the pump flow noise and described the noise as "indications of cavitation." The pump was immediately shut down and the system engineer contacted. Later that evening, the pump was restarted to monitor for indications of cavitation; however, none were noted and the pump was determined to be operable. The licensee decided to conduct more extensive tests, including tests to determine the pump head curves, and began the tests on June 21. The licensee plans to investigate the possibility of governor valve stem binding. The licensee reported that the valve stem is the older, gas nitrided, 410 stainless variety. The licensee planned to disassemble the valve and possibly replace the valve stem with an inconel stem if one can be obtained or manufactured. Additionally, the licensee is investigating the cause of the excessive amount of water from both the stack vent and the sentinel valve. Finally, the licensee was bringing vendor representatives from both Dresser and Woodward to assist in the root cause analysis. Regional Action: Resident and regional inspectors will monitor the licensee's activities including turbine repairs and retests. Contact: Harry Freeman (817)897-1500